hiseamarine

FX-TFOI VFD Cable

[Search Related Products]

FX-TFOI VFD Cable


Application

VFD Cable is specifically designed to combat the problems of system performance and signal disruption. When generic cables degrade over time, this keeps VFD systems running with required precision. With new levels of flexibility, it makes routing and installation fast and easy.


FX-TFOI VFD Cable standards

- Design guide : IEC 60092-350 & IEC 60092-353

- Insulation material : IEC 60092-351, XLPE

- Sheath material : IEC 60092-359, SHF1
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Halogen content : IEC 60754-1, 0.5%
- Smoke emission : IEC 61034, 60%
- Cold bend/impact : CSA 22.2 No. 0.3 (-40¡ã / -35¡ã )

- Max. rated conductor temperature : 90¡ã¡æ


FX-TFOI VFD Cable construction

Classification Code Construction detail
Conductor FX

- Stranded plain annealed copper wires as per IEC 60228, Class 5

- A suitable tape may be applied on the conductor

Insulation T - XLPE as per IEC 60092-351
Cabling
- Insulated conductors shall be cabled

- Flame retardant & non-hygroscopic fillers may be used

- Suitable tape(s) may be applied on the cabled core

- A Filler may be applied to obtain a circular Cable
Inner covering F Non-hygroscopic material
Armor(Screen) (VFD) - CU/PS Tape providing 100% Coverage
O - Braid of plain annealed copper wire
- Coverage density : Min. 90%
Sheath I

- SHF1 as per IEC 60092-359

- Sheath color : Black

We will provide you with the best quality, competitive prices and satisfactory service.

For more enquiries ,please contact freely at cable@hiseamarine.com

Contact with us now

Our mail: manager@hiseamarine.com

Change Image